(RVT, RD, RBTR Types – frame or grate switchgears for indoor brick and kiosk transformer stations)
RD, RVT, RBTR switchgears are LV switchgears designed for internal spaces of transformer stations 10, 22, 35 / 0.4 kV of the power up to 1×630 kVA or 2×630 kVA. These switchgears are designed and manufactured in compliance with ČSN EN 61 439-1 ed.3, ČSN EN 61 439-2 ed.3 and ČSN EN 61 439-5 ed.2 standards.
Technical specifications:
Nominal voltage: 3×400 / 230 V / TN-C, 50Hz
Nominal current of main busbars: max. 1000 A
Switchgear short-circuit resistance: 35 kA / 1 s
Protection against dangerous contact voltage: by automatic disconnection from the power supply
Switchboard cover: IP 20/00
Structure: welder steel frame from U-profile 35x35x3 mm or bolted from perforated profiles
Sheathing: 1.5 mm (or 2 mm) steel sheet
Surface finish: powder coating (RAL 7032, 7035, or as requested by the customer)
Basic dimensions [mm]:
a) RD, RVT switchgear:
width: according to the number of outlets, 600 to 1000 mm
height: 2000 mm
depth: 400, 500 mm
b) RBTR frame switchgear:
width: 1000 to 2000 mm
height: 1200 mm
depth: 300 to 450 mm
c) RBTR grate switchgear:
width: 1000 – 1200 mm
height: 1350, 1800 mm
depth: 300 mm
Tento web používá soubory cookie ke zlepšení vašeho zážitku při procházení webem. Z nich jsou cookies, které jsou kategorizovány podle potřeby, uloženy ve vašem prohlížeči, protože jsou nezbytné pro fungování základních funkcí webových stránek. Používáme také soubory cookie třetích stran, které nám pomáhají analyzovat a porozumět tomu, jak tento web používáte. Tyto soubory cookie budou ve vašem prohlížeči uloženy pouze s vaším souhlasem. Máte také možnost se z těchto cookies odhlásit. Ale odhlášení některých z těchto souborů cookie může ovlivnit váš zážitek z prohlížení.